CASING - Standard panels shall be 20 gauge galvanized steel. The housing shall be supported by a formed structural base that forms a pan to ensure weather tight construction. Lifting holes shall be provided at the unit base. Units shall have a weatherproof sheet metal roof. Insulation shall be ½” thick closed-cell neoprene for wash down capability and include antimicrobial protection. Insulation shall meet or exceed requirements of UL 181, ASTM G21/C 1338 and ASTM G 22 for resistance to mold, fungi and bacteria. The outdoor air intake opening shall be protected by a galvanized steel sheet metal weather hood and include an automatic rotary blade damper with blade seals and an electric actuator. The exhaust air discharge shall be covered with a gravity back draft damper and weather hood. The exterior of the unit shall be coated with an epoxy primer and a polyurethane enamel painting system for added protection. Painting system shall be rated to meet a 1500-hour salt spray test.
ACCESS - Access to components shall be provided through a large, tightly sealed and easily removable access panel. Access panels shall be constructed of the same materials as the unit casing and use SEMCO's standard hardware. The wheel cassette shall be easily removable from the unit. The roof of the unit shall also be removable for access.
UNIT CONFIGURATION - The supply air inlet and exhaust air outlet must be oriented at opposite ends of the Energy Recovery System to maximize the distance between the two air streams in order to minimize the risk of short circuiting exhaust air into the supply air intake.
Fans - Fans shall be double width double inlet design with forward curve type wheels. The blades shall be designed for maximum efficiency and quiet operation. Impellers shall be statically and dynamically balanced.
Fans shall be driven by direct drive motors located at the fan inlet or by motors using belts and sheaves. Motors shall be standard NEMA frame with open drip-proof enclosures. V-belt drives shall be designed for a minimum 1.2 service factor.
Confirm inclusion or delete Remote Indicating Panel – Panel shall provide remote indication of status of unit power on, wheel rotation alarm, outside air dirty filter and return air dirty filter. Low voltage LED’s will be illuminated for power on, wheel stop, filter pressure drop exceeding 0.8” w.c. LED’s are factory mounted in a brushed aluminum faceplate with identification label and are factory wired to a terminal strip. Panel includes a junction box and plaster ring for either recessed or surface mounting. FV unit will include factory mounted pressure switches and electrical components wired to a terminal strip located in an exterior weatherproof junction box. Field wiring between the FV unit and the remote panel using Belden 5 conductor 8465 (20-gauge) or equivalent.
Confirm inclusion or delete Dual Wall Construction – Unit shall be equipped with an interior liner of 22 gauge galvanized sheet metal.
Confirm inclusion or delete Electric Preheat Coil - Coil shall be of the resistance coil type with elements enclosed in a steel sheath with fins and painted with a baked-on aluminum paint for long life in a 100% fresh air stream. Coil shall include thermal cutout protection with automatic primary protection and a secondary manual reset linear thermal cutout. Coil shall have magnetic safety and backup contactors, main disconnect, fusing, control circuit transformer, airflow interlock switch and SCR controller. Coil shall be UL listed and constructed in accordance with NEC requirements. A temperature controller located in the outdoor air section of the unit shall supply the signal to the SCR controller.
Freeze Protection Thermostat - Unit shall be equipped with an outdoor air temperature thermostat such that the energy recovery ventilator can be stopped during very low temperature periods. This thermostat shall stop the fans and the energy recovery wheel until the outdoor air temperature rises above the set-point, then the unit will restart automatically.
Electrical - Units shall require a single 60-cycle power connection. See schedule for voltage and phase requirements. The electrical panel shall consist of individual motor contactors, short circuit and overload protection, and a control power transformer. The NEMA 3R electrical panel shall be mounted on the unit exterior for ease of access. Unit shall be ETL listed and labeled.
Warranty - SEMCO warrants to Buyer that for a period of eighteen months from the date of shipment by SEMCO, the goods to be delivered to Buyer will in all material respects be free from defects in material and workmanship when used in a proper and normal manner. Should any failure to conform to the above appear within eighteen months after the date of shipment by SEMCO (the "Limited Warranty Period"), SEMCO agrees upon prompt notification thereof during the Limited Warranty Period and confirmation to SEMCO's satisfaction that the goods have been stored, installed, operated and maintained properly and in accordance with standard industry practice, to correct the non-conformity at SEMCO's option either by repairing any defective part or parts or by making available at SEMCO's plant a repaired or replacement part.
WHEEL WARRANTY: Manufacturer shall warrant to the buyer for a period of 60 months that the wheel contained in the energy recovery unit in all material respects to be free from defects in material and workmanship when used in a proper and normal manner. For warranty purposes the wheel includes, media, desiccant coating, wheel hub, wheel rim and spokes